DESCRIPTION
Supracontrol RC102 is IP controller intended for managing and monitoring operational conditions in telecommunications and servers enclosures. One controller supports two identification devices, two electric locks, four magnetic door sensors for access control, four BUS485 inputs for connecting additional sensors and peripheral devices, such as ports for digital input and general purpose relays. Controller can work in offline mode - completely independent, or in online mode - connected to the Supracontrol Enterprise application. In offline mode, to controller can be accessed through the integrated web console. Controller can connected on the secondary power supply or backup SLA battery.
FEATURES
- Two ports for identification devices with RS485 or Wiegand communication interface
- Two ports for electric locks or electromagnets with possibility of choice between 12 VDC or 24 VDC power supply
- Four ports for magnetic door sensors
- Four non - powered digital inputs for additional sensors or peripheral devices
- Two latching relays for managing of supported devices
- Four RS485 BUS ports to connect sensors
- Auto discovery protocol to connect RS485 devices or sensors
- Ethernet 10/100 Base-T communication interface
- Communication via secured HTTPS protocol (SSL/TLS 1.2)
- Supported protocols: TCP/IP, HTTP, HTTPS, SSL/TLS 1.2, DS, DHCP, NETBIOS, SMTP
- Integrated web server with application for configuration, monitoring and managing of device
- Power supply via an external adapter
- Port for secondary, redundant power supply
- Port for power supply via battery, Sealed Lead Acid (SLA) battery, 12 V, 7.2 Ah
- Integrated Real Time Clock (RTC) interface
- Power supply for external devices, 12 VDC max: 150 mA
- Integrated short circuit and overload protection
- Works in online and offline mode
SPECIFICATIONS
Signalization | Power supply (green LED), alarm (red LED) |
Communication interface | Compatible to Ethernet 10/100Base-T network |
Protocol | TCP/IP, UDP. HTTP, SMTP, SNMP, DHCP, DNS,NetBIOS, HTTPS, SSL/TLS 1.2 |
Port | 1 RJ45 Ethernet 2 identification devices (RFID readers for front and back door) 4 Magnetic sensors (front, back and side door) 2 electric locks (front and back door) 4 digital inputs 2 relay outputs 4 RS485 BUS sensors 2 Power supply ports 1 Port for battery |
Identification device | Communication: RS485 or Wiegand Type: RFID readers, bio metric readers, keyboards Power supply: 12 VDC, max 150 mA Output signalization: access authorized (green LED) access denied (red LED) Buzzer |
Electric locks | Type: Fail safe or Fail secure Power supply: 12 VDC, max 500 ma/24 VDC, max 250 mA |
Digital inputs | 2 latching general purpose relays |
BUS sensors | 4 SupraBUS inputs for sensors to monitor operational conditions Power supply: 12 VDC, max 150 mA per port |
Power input | Primary and secondary (redundant) power supply, 12 VDC, min 5 A |
Backup power | Sealed Led Acid (SLA) battery 12 VDC, mad 7.2 Ah |
Autonomy |
4-8 hours, depends to connected devices |
Operating conditions |
Temperature: -20 - 80 ºC |
Storage conditions |
Temperature: -20 - 80 ºC Humidity: 10 - 95 %RH (non-condensing) |
Power consumption | Max 2.5 A @ 12 VDC |
Dimensions (non-packing) | Height: 125 mm Width: 175 mm Depth: 45 mm |