DESCRIPTION
Supracontrol BC100 is an IP-based controller designed for monitoring of operating conditions in datacenters, telecommunication and server racks and other industrial applications. A single controller supports 8 BUS ports for connecting up to 64 BUS sensors and detectors such as temperature, humidity, smoke, flood, vibration, particle sensor and other peripherals from Supracontrol BUS line. It is equipped with general purpose digital inputs and relay outputs. The controller can work either in Offline mode, completely autonomously, or in Online mode, connected to Supracontrol Enterprise software. When in Offline mode, the controller can be accessed and managed locally through integrated web management console. The controller supports connection to two independent power sources (redundant power supply) and a backup SLA battery using optional internal Battery Charger with UPS function.
FEATURES
- Eight SupraBUS sensor inputs for connecting up to 64 Supracontrol BUS peripheral devices
- Two latching relay outputs for 3P device control
- Four digital inputs for monitoring UPS, diesel generator, air condition, alarm detector, etc
- Ethernet 10/100Base-T communication interface
- Communication via secure HTTPS protocol (TLS 1.2)
- Built-in web server with embedded management software
- Integrated RTC (Real Time Clock) interface
- Alarm notifications via email, SMS, voice or mobile
push notifications - More than 200.000 stored logs
- Supports Online and Offline modes
- Firmware updates over IP network
- API for 3P integration
- Two independant power inputs
SPECIFICATION
Indicators | Power (green LED), Alarm (red LED) |
Communication interface | Ethernet 10/100Base-T Networks compatible |
Protocols | TCP/IP, UDP, HTTP, SMTP, SNMP, DHCP, DNS, NetBIOS, HTTPS, SSL/TLS 1.2 |
Ports | Front side: 8 SupraBUS ports, RJ45 connector Back side: 1 AUX power output for I/O supply, 2 way terminal block connector 4 Digital inputs, 4 way terminal block connector 2 Relay outputs, 2 way terminal block connector 1 Ethernet port, RJ45 connector 1 SLA Battery input, 2 way terminal block connector 2 Power inputs, 2 way terminal block connector (PPS - Primary Power Supply SPS - Secondary Power Supply) |
Digital port | 4 General-purpose digital inputs, (5 – 24 V DC) Power supply: 12 V DC, max 250 mA Type: Sourcing |
Digital port | 2 General-purpose latching relays 60 VA |
BUS port | 8 SupraBUS inputs Power supply: 12 V DC, max 250 mA per port |
Power input | 12 V DC |
Backup power | Passive PoE, 12 V DC via Ethernet connector |
Power consupmtion | Max 250mA @ 12 V DC |
Operating conditions | Temperature: -20 – 80 ºC Relative humidity: 10 – 95 % RH (non-condensing) |
Storage conditions | Temperature: -20 – 85 ºC Relative humidity: 0 – 95 % RH (non-condensing) |
Dimensions (w/o packaging) | Height: 125 mm Width: 175 mm Depth: 45 mm |
Weight | Netto: 574 g |
Packaging | Height: 125 mm Width: 175 mm Depth: 45 mm Weight: 1639 g |